Improving Network Fault Protection at 20/0.4 kV for General Hospital Operations through ETAP Simulation-Based Protection Relay Re-Setting
DOI:
https://doi.org/10.38035/ijam.v5i2.2278Keywords:
Protection Relay, OCR-GFR, Protection Coordination, ETAP, Hospital Electrical SafetyAbstract
Fires caused by electrical disturbances are a major cause of material loss and safety risk in hospital buildings, particularly from short-circuit faults that are not selectively isolated by the existing protection system. This study evaluates the performance of the 20/0.4 kV distribution network protection system in a type-B general hospital and formulates a re-setting of the Over Current Relay (OCR) and Ground Fault Relay (GFR) to satisfy the principles of selectivity, sensitivity, reliability, and speed. A quantitative method with an ETAP 19.0.1 simulation approach was used, supported by field observation and historical fault data. The results show that the existing protection coordination has a grading margin of less than 0.2 seconds between relay levels, resulting in non-selective operation, consistent with a laboratory fire incident that was not isolated quickly. After re-setting based on short-circuit simulation and Time Current Characteristic (TCC) curve analysis, the protection coordination becomes selective, with a total clearance time on the priority feeder below 1.5 seconds and a considerably narrower outage area. This study recommends implementing the new settings together with primary injection testing and standardized documentation procedures for the hospital's electrical team.
References
Badan Standardisasi Nasional (BSN). (2011). PUIL 2020: Persyaratan Umum Instalasi Listrik 2020 (SNI 0225:2011). BSN.
Çalışkan, E. (2025). Application of adaptive protection relays in hospital trigeneration systems and analysis using ETAP software. Yildiz Technical University.
ETAP Technical Team. (2023). Integrated solutions for protection & coordination. ETAP.com.
Hassan, M., et al. (2022). Protection coordination in hospital microgrids. Elsevier.
IEEE. (2021). IEEE Std 602 (IEEE White Book): Electric systems in health care facilities. IEEE.
Irwanto, et al. (2021). Short circuit analysis on distribution network 20 kV using Etap software. Jurnal Ojs.unimal.ac.id.
Marchese, A., et al. (2015). Protection selectivity analysis in electric system for hospital application. Part I: Radial and loop distribution. INFONA.
Mardiyah, S. (2023). Evaluasi instalasi listrik pada rumah sakit berdasarkan PUIL 2011: Suatu studi kasus pada rumah sakit swasta di Jakarta Timur. Perpustakaan UNJ.
Munir, M. (2022). Optimal coordination of power protective devices with illustrative examples. Wiley.
National Fire Protection Association (NFPA). (2018). NFPA 99: Health care facilities code. NFPA.
Novrianti, N. (2022). Analisa indeks keandalan dengan penambahan recloser pada sistem distribusi 20 kV Penyulang Makassar di Gardu Induk Talang Ratu menggunakan metode section technique dan ETAP. Repository Unsri.
Permana, D., & Handayani, R. (2020). Analisis koordinasi rele arus lebih pada Penyulang Pujon terintegrasi dengan pembangkit tersebar. Garuda Kemdikbud.
Prasetyo, B. (2023). Studi analisis koordinasi proteksi rele differential dan rele overcurrent pada transformator menggunakan software ETAP 12.6. Repository UMY.
Regoli, F., et al. (2015). Service continuity safety by design: The relevance of electrical power-system architectures in hospitals. IEEE Xplore.
Sari, D., et al. (2023). Evaluasi perencanaan sistem kelistrikan Rumah Sakit “X” berdasarkan PUIL 2011 dan aplikasi Ecodial. Petra.
Sihombing, R., et al. (2019). Analisis koordinasi rele arus lebih, recloser, dan fuse pada jaringan distribusi 20 kV. Repositori USU.
Sitorus, H., et al. (2024). Electrical safety improvement in Ngaliyan public health facility on Semarang City. IEEE Xplore.
Utami, R., et al. (2026). Harmonic distortion assessment of nonlinear medical loads in a hospital distribution network using ETAP simulation. Ecotipe UBB.
Yuliza, N., et al. (2023). Analisis setting over current relay 1 fasa ke tanah sistem 20 kV pada Recloser B21 berbasis ETAP. Paperity.
Zaini, A. (2021). Relay coordination studies. Polyenergy.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2026 Mochamad Aminudin, Abdul Multi, Agus Sofwan

This work is licensed under a Creative Commons Attribution 4.0 International License.
Authors who publish their manuscripts in this journal agree to the following conditions:
- The copyright on each article belongs to the author(s).
- The author acknowledges that the International Journal of Advanced Multidisciplinary (IJAM) has the right to be the first to publish with a Creative Commons Attribution 4.0 International license (Attribution 4.0 International (CC BY 4.0).
- Authors can submit articles separately, arrange for the non-exclusive distribution of manuscripts that have been published in this journal into other versions (e.g., sent to the author's institutional repository, publication into books, etc.), by acknowledging that the manuscript has been published for the first time in the International Journal of Advanced Multidisciplinary (IJAM).